Robert:

The pressure drop across the 220 Sensor is of course a function of the pipe size it is installed into; which they did not provide.

 

We stop taking head loss measurements at 2”, since the head loss becomes too hard to measure in larger pipe sizes.

 

However, for design purposes, they should consider the head loss to be the same as 5 Feet of the same size pipe..

 

For example, the head loss in through a 4” pipe at 200 GPM is about 0.985 PSI/100 Ft, so 5 Ft would be about 0.049 PSI or 1.36 Inches of Water.

 

As you can see, the head loss to truly negligible.

 

 

 

Regards,

Ronald Purdy

 


Ronald Purdy | Senior Sales Engineer | Office: 1.414.371.7233  | rpurdy@badgermeter.com | www.badgermeter.com

Badger Meter | 4545 W Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536

 

From: Robert Jarosinski [mailto:RJarosinski@maidaintl.com]
Sent: Wednesday, November 23, 2016 10:05 AM
To: Purdy, Ronald
Subject: [EXTERNAL] FW: Flow sensor

 

Good Morning Ron:

 

Below is an email we received from Honeywell in the UAE. We quoted them 220SS and a 310. Can you give us the best respond we could use. In the past we used a data sheet to show a negligible drop in pressure but we cannot come up with that info.

Thank you in advance.

 

Have a Happy Thanksgiving.

 

 

Best Regards

Robert Jarosinski

cid:image001.jpg@01D06877.4873F420

 

 

 

 

From: Thaha, Sabitha [mailto:Sabitha.Thaha@Honeywell.com]
Sent: Wednesday, November 23, 2016 2:35 AM
To: Robert Jarosinski
Cc: Ahmad, Nisar
Subject: RE: Flow sensor

 

Hi Robert

 

Please see my below email, I have not asked for the quote. I have asked for the pressure drop across this sensor as we are planning to submit these flow sensor for one our project and the consultant has asked us this query.

 

Please respond to this urgently!!!

 

 

 

 

 

 

Best Regards

 

 

Sabitha Thaha

Sr.Solution Advisor

 

Honeywell Building Solutions

Emaar Business Park

Building 2, Level 2,

P.O. Box 232362,

Dubai, United Arab Emirates

 

Phone: +971 4 4505 935 (Direct)

Phone: +971 4 4505 800 (Switch)
Fax:     +971 4 4505 900

Mobile: +971 56 685 3984

Email: sabitha.thaha@honeywell.com

 

From: Robert Jarosinski [mailto:RJarosinski@maidaintl.com]
Sent: Tuesday, November 22, 2016 11:00 PM
To: Thaha, Sabitha
Subject: RE: Flow sensor

 

Dear Sabitha:

 

Enclosed please find our quote 015510. 2 week delivery to our office.

 

Best Regards

Robert Jarosinski

 

 

cid:image001.jpg@01D06877.4873F420

https://gallery.mailchimp.com/305ecf782917f5820c6f3a3f8/images/ade59fbd-13b4-419c-b1c1-91aad23d82e0.png

 

 

 

From: Thaha, Sabitha [mailto:Sabitha.Thaha@Honeywell.com]
Sent: Tuesday, November 22, 2016 6:11 AM
To: Robert Jarosinski
Cc: Ahmad, Nisar
Subject: Flow sensor

 

Hi Robert

 

Can you please confirm the pressure drop of the below flow sensor.

 

 

Maida

220SS0005-1211

WATER FLOW SENSOR-TURBINE TYPE

310-00

PROGRAMMABLE ANALOG TRANSMITTER

 

 

 

 

 

 

Best Regards

 

 

Sabitha Thaha

Sr.Solution Advisor

 

Honeywell Building Solutions

Emaar Business Park

Building 2, Level 2,

P.O. Box 232362,

Dubai, United Arab Emirates

 

Phone: +971 4 4505 935 (Direct)

Phone: +971 4 4505 800 (Switch)
Fax:     +971 4 4505 900

Mobile: +971 56 685 3984

Email: sabitha.thaha@honeywell.com